Control Equipment & Motor Switchgear

Distribution Boxes(Motor Starters) Explosion-proof HLDP03-K

Distribution Boxes(Motor Starters) Explosion-proof HLDP03-K

Application

  • Zone 1 and Zone 2
  • Zone 21 and Zone 22
  • Meet the necessities in the following industries, such as petroleum, chemical, electricity, medicine, textile, wine-making, aerospace, military, fire-fighting, etc.

Features and benefits

  • Explosion protection to
    -CENELEC
    -IEC
  • Copper-free aluminium enclosure; powder-coated surface.
  • Built-in MCB (mini circuit breaker), MCCB (moulded circuit breaker).
  • Electric leakage protection device is optional.

Categories: Control Equipment & Motor Switchgear, Helon Indonesia

Application

  • Zone 1 and Zone 2
  • Zone 21 and Zone 22
  • Meet the necessities in the following industries, such as petroleum, chemical, electricity, medicine, textile, wine-making, aerospace, military, fire-fighting, etc.

Features and benefits

  • Explosion protection to
    -CENELEC
    -IEC
  • Copper-free aluminium enclosure; powder-coated surface.
  • Built-in MCB (mini circuit breaker), MCCB (moulded circuit breaker).
  • Electric leakage protection device is optional.
Explosion protection
Gas explosion protectionII2 G Ex d IIB T6 Gb
Dust explosion protectionII2 D Ex tb IIC T80℃ Gb IP66
Conformity to standardsEN 60079-0:2012,EN60079-1:2007,EN6007979-31:2009
IEC 60079-0:2011,IEC60079-1:2007,IEC60079-31:2008
Enclosure materialAluminium alloy; powder coated surface
Enclosure colourgray-white with mental lines
Enclosure fastenerStainless steel
Degree of protectionIP66
Ambient temperature-60℃~+55℃
Cable gland(optional)Ex d is recommended
Entry directionBottom
Electric leakage protectionOn request
Circuit breakerMCB (mini circuit breaker)
Max.working voltage440V AC 50.60Hz
Rated voltage1P/230V AC,2P/3P/4P/400V AC 50/60Hz
Rated current1A,2A,4A,6A,10A,16A,20A,25A,32A,40A,50A,63A
Pole number1P,2P,3P,4P
Breaking capacity6kA, 10kA, 15kA
Tripping characteristicInstantaneous tripping range (5~10) In, (7~10) In or (10~14) In
Impulse withstand voltage6kV
Cable entriesStandard 1~16A:2×M25×1.5 plug
20~32A:2×M32×1.5 plug
40~63A:2×M40×1.5 plug
Circuit breakerMCCB (moulded case circuit breaker)
Rated working voltage690V AC 50/60Hz
Rated working current80A, 100A, 125A, 160A
Pole number3P, 4P
Breaking capacity380/415V AC 50/60Hz, 36kA/50kA
440V AC 50/60Hz,30kA/45kA
Impulse withstand voltage8kV
Tripping deviceThermomagnetic type
Cable entries Standard 80~100A:2×M50×1.5 plug
125~160A:2×M63×1.5 plug
Circuit breakerMCCB (moulded case circuit breaker)
Rated working voltage690V AC 50/60Hz
500V DC
Rated working current200A, 250A
Pole number3P, 4P
Breaking capacity380/415V AC 50/60Hz, 36kA/50kA
440V AC 50/60Hz,25kA/40kA
Impulse withstand voltage8kV
Tripping deviceThermomagnetic type
Cable entries Standard 2×M63×1.5 plug
NoteRated current>250A on request